Conducted currents can be measured without making direct contact with the source conductor or metallic surface by means of clamp-on broadband current probes. The BCP-5xx EMC Current Probes are designed to permit field intensity meters, spectrum analyzers, and other 50W impedance instruments to measure quantitative magnitudes of current. Measurements can be made on single and multi-conductor cables, ground and bonding straps, shielded conduits and on coaxial cables.



Model

Frequency
Range
Transfer Impedance (dB ohms) Max Cont. Current (Amps)
Aperture (in.)

Diam. (in.)
BCP-510 20 Hz - 1 MHz -56 to -30 100 1.2 3.9
BCP-511 20 kHz - 100 MHz -12 to +1 350 1.2 3.9
BCP-512 1 MHz - 1 GHz 0 to 24 200 1.2 2.8
BCP-514 10 kHz - 100 MHz -18 to 0 350 2.7 5.0
BCP-515 1 MHz - 400 MHz -14 to 19 300 1.2 2.8
BCP-516 10 kHz - 50 MHz -7 to 12 800 1.2 3.7
BCP-518 100 kHz - 500 MHz -10 to 15 200 2.7 5.0
BCP-519 100 Hz - 100 MHz -40 to 17 200 2.6 5.5
BCP-520 10 KHz - 500 MHz -19 to 20 350 1.2 3.9
BCP-522 1 KHz - 200 MHz -30 to 0 100 1.2 2.8
BCP-526 100 KHz - 1 GHz -20 to -14 350 1.2 3.9



Injection Current Probes

Injection Current Probes are used to inductively couple large RF currents into conductors passing through their aperture. The conductors are signal, control and power circuits of equipment under test for conducted susceptibility or immunity.

Typical specifications requiring the use of injection probes are:
· DO-160
· EN-50081-1
· IEC 801-6
· TR-EOP-000063

Model Frequency Range Insertion Loss (dB) Max Cont. Input Power (Watts) Aperture Diam.
ICP-521 10 kHz - 100 MHz 12 to 33 100 1.6" (40 mm) 5" (127 mm)
ICP-522 1 MHz - 400 MHz 4 to 22 200 1.6" (40 mm) 5" (127 mm)
ICP-523 300 kHz - 1000 MHz 4 to 16 100 1.6" (40 mm) 5" (127 mm)



Current Probe Fixtures

The A.H. Systems' line of Current Probe Calibration Fixtures are a great way to keep your broadband Current Probes, and Injection Current Probes calibrated and up to date.  Their rugged design ensures long life, and faultless operation over the wide calibration frequency range of 10 kHz to 1000 MHz.

Current Probe Fixtures
CPF-530 10 kHz - 400 MHz Calibration Fixture
CPF-531 1 MHz - 1000 MHz Calibration Fixture
CPF-532 10 kHz - 400 MHz Calibration Fixture, Oversize